docs(moteur): « Comment le moteur décide » aligné sur le code des règles
Relu contre le moteur (main 61db6cf) : en temps réel la protection ne bride que les bornes,
les autres charges sont délestées au cycle suivant ; cycle chaque minute ; repli à 90 s de
silence du compteur, états sûrs. Ordre réel : mesure et marge de soutirage, échéances VE,
réserve batterie, passe éco (demandes ponctuelles puis obligations étalées) avant la cascade
confort ; recrédit, plancher, verrous et indisponibilité appliqués charge par charge ; une
commande par charge. Retiré : « si l'installateur l'a autorisé » (aucune autorisation dédiée).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Ry3vBrJT1tHdxAaXdCWi6L
2026-10-18 13:54:11 +02:00

65 lines
3.1 KiB
Markdown

# Optimizer
<span class="badge testing">IN PROGRESS</span>
The protocol between the engine and an optimizer is published (version 1.1). Connecting
an optimizer is being tested on our test installation; the box does not need one to work.
## What an optimizer is for
The [engine's rules](../fonctionnalites/moteur.md) decide on the present: this minute's
surplus, shared according to your priorities. An optimizer looks further ahead. From the
forecasts the engine hands it — PV production, base consumption, entered tariff — it
proposes a **plan in time slots** over several hours: shift the water heater to the
expected production peak, keep headroom for evening charging, and so on.
## The optimizer advises, the engine decides
- The engine only executes the **current slot** of the plan. The rest is shown as a
forecast, and requested again on the next cycle.
- Every setpoint is **capped** by the load's bounds (floor, ceiling, anti-flapping locks)
and by the **overload protection** ([How the engine
decides](../fonctionnalites/moteur.md)), which stays with the engine and overrides
everything. An optimizer cannot bypass a lock.
- Every action must carry its **reason**. An action without one is rejected.
- A malformed plan, or one that targets an unknown load, is rejected as a whole.
At worst, a faulty optimizer can therefore only propose a poor allocation — bounded by the
engine.
## The box works without an optimizer
Optimizer missing, silent, abstaining, plan expired or rejected: the engine returns to its
**rules** (`rules`) for that cycle, with no interruption of control. The app shows at all
times which strategy is in charge. The Community edition works entirely this way.
## Its data come from the engine only
- The engine connects to the optimizer, never the other way round: the box opens no port.
- The optimizer runs on the box (local socket) or on a machine in your local network
(TCP). On the local network, a shared secret (token) is recommended.
- It receives **only** the context the engine sends, forecasts included: it calls neither
a weather service nor a tariff provider, and opens no connection to the outside.
- What it learns stays on site.
## Who can write an optimizer
Anyone. The protocol is open and described by a [machine-readable contract](contrat.md)
published under GPL-3.0. A free **reference optimizer** and a **conformance suite** let you
write your own and check it against the real engine — see
[Writing an optimizer](ecrire.md).
## The ETM optimizer
ETM-Schurig offers its own proprietary optimizer, included in the Pro edition. It connects
through this same protocol, within the same limits: it advises, the engine decides. At
handshake it announces itself as `etm-optimizer`; the reference optimizer announces itself
as `powersync-optimizer`.
## In this section
- [Protocol](protocole.md) — transport, handshake, context, plan, fallback, validation
rules.
- [Contract](contrat.md) — the OpenRPC file that is authoritative on the shape of messages.
- [Writing an optimizer](ecrire.md) — reference optimizer and conformance suite.