Via Unit 0,Via Unit 3,R/W,Content,Category
200,0,RW,Relay Output 3.1,Basic
201,1,RW,Relay Output 3.2,Basic
202,2,RW,Relay Output 3.3,Basic
203,3,RW,Relay Output 3.4,Basic
204,4,RW,Relay Output 3.5,Basic
205,5,R,Digital Input 3.1,Basic
206,6,R,Digital Input 3.2,Basic
207,7,R,Digital Input 3.3,Basic
208,8,R,Digital Input 3.4,Basic
1200,1000,RW,MWD reset indication,Advanced
1202,1002,R,Reset group MCU,Advanced
1203,1003,RW,Save current configuration and use on startup,Advanced
1204,1004,RW,(Internal) Firmware programming toggle,Expert
1205,1005,RW,(Internal) Firmware reprogramming toggle,Expert
1206,1006,RW,(Internal) Firmware calibration programming toggle,Expert
1207,1007,RW,Enable DirectSwitch on DI 3.1,Advanced
1208,1008,RW,Enable DirectSwitch on DI 3.2,Advanced
1209,1009,RW,Enable DirectSwitch on DI 3.3,Advanced
1210,1010,RW,Enable DirectSwitch on DI 3.4,Advanced
1211,1011,RW,Invert DirectSwitch Polarity on DI 3.1,Advanced
1212,1012,RW,Invert DirectSwitch Polarity on DI 3.2,Advanced
1213,1013,RW,Invert DirectSwitch Polarity on DI 3.3,Advanced
1214,1014,RW,Invert DirectSwitch Polarity on DI 3.4,Advanced
1215,1015,RW,Enable DirectSwitch Toggle Mode on DI 3.1,Advanced
1216,1016,RW,Enable DirectSwitch Toggle Mode on DI 3.2,Advanced
1217,1017,RW,Enable DirectSwitch Toggle Mode on DI 3.3,Advanced
1218,1018,RW,Enable DirectSwitch Toggle Mode on DI 3.4,Advanced