docs(moteur): schémas Mermaid — vue d'ensemble des briques, rangs et domaines
All checks were successful
Build & Deploy docs / build-deploy (push) Successful in 3m32s
All checks were successful
Build & Deploy docs / build-deploy (push) Successful in 3m32s
Vue d'ensemble : entrées, protection contre la surcharge, cycle de répartition en six étapes, optimiseur en option, adaptateurs, charges. Rangs et domaines : une seule liste pour le moteur ; les domaines ne servent qu'à l'affichage de l'app, un chauffe-eau peut être servi en dernier. Encadré : une borne détectée arrive en fin de liste. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Ry3vBrJT1tHdxAaXdCWi6L
This commit is contained in:
parent
e6a5f50467
commit
01a0db7d25
@ -7,6 +7,48 @@ Warmwasserbereiter, SG-Ready-Wärmepumpe, Relais. Sie ist frei (GPL-3.0) und ent
|
||||
der **Community**-Version. Diese Seite beschreibt ihre Logik für Installateure und
|
||||
Integratoren; die folgenden Seiten erläutern die einzelnen Funktionen.
|
||||
|
||||
## Überblick
|
||||
|
||||
```mermaid
|
||||
flowchart TB
|
||||
CPT["Netzanschlusszähler<br/>Strom je Phase, Einspeisung, Bezug"]
|
||||
BAT["Batterie<br/>Ladezustand"]
|
||||
APP["App<br/>einmalige Anforderungen"]
|
||||
CFG["Einstellungen des Installateurs<br/>Ränge, Grenzen, Pflichten"]
|
||||
|
||||
subgraph M["Energie-Engine, auf der Box"]
|
||||
PROT["Überlastschutz<br/>bei jeder Messung, vorrangig"]
|
||||
subgraph C["Verteilungszyklus, jede Minute"]
|
||||
C1["1. Messung und Bezugsspielraum"] --> C2["2. Ladefristen"]
|
||||
C2 --> C3["3. Batteriereserve"]
|
||||
C3 --> C4["4. Eco-Durchlauf<br/>einmalige Anforderungen, Pflichten"]
|
||||
C4 --> C5["5. Komfort-Durchlauf<br/>Überschuss kaskadiert, nach Rang"]
|
||||
C5 --> C6["6. Ein Befehl pro Verbraucher"]
|
||||
end
|
||||
AD["Adapter<br/>Grenzen und Sperren jedes Verbrauchers"]
|
||||
end
|
||||
|
||||
OPT["Optimierer, optional<br/>schlägt die Verteilung vor"]
|
||||
|
||||
VE["Wallboxen"]
|
||||
ECS["Warmwasserbereiter<br/>per Relais oder regelbar"]
|
||||
PAC["SG-Ready-Wärmepumpe"]
|
||||
REL["Relais"]
|
||||
|
||||
CPT --> PROT
|
||||
CPT --> C1
|
||||
BAT --> C3
|
||||
APP --> C4
|
||||
CFG --> C
|
||||
OPT -. "Plan" .-> C6
|
||||
C6 --> AD
|
||||
PROT --> AD
|
||||
AD --> VE & ECS & PAC & REL
|
||||
```
|
||||
|
||||
Überlastschutz und Adapter bleiben in jedem Fall bei der Engine: Ein
|
||||
[Optimierer](../optimiseur/index.md) schlägt, falls angeschlossen, nur die Verteilung vor.
|
||||
|
||||
## Zwei Schleifen, zwei Prioritäten
|
||||
|
||||
Die Engine trennt Sicherheit und Verteilung. Es sind zwei getrennte Schleifen, mit
|
||||
@ -68,6 +110,48 @@ In jedem Zyklus durchläuft die Engine dieselben Schritte, in derselben Reihenfo
|
||||
Verbrauchers werden zusammengeführt: Jeder Verbraucher erhält einen einzigen Sollwert,
|
||||
mit seinem Grund.
|
||||
|
||||
### Ränge und Domänen
|
||||
|
||||
Die Engine kennt **nur eine einzige Liste**: Jeder Verbraucher hat einen Rang, über alle
|
||||
Kategorien hinweg, und die Kaskade folgt diesem Rang. Die **Domäne** eines Verbrauchers
|
||||
(Elektrofahrzeug, Warmwasser, Klimatisierung, Heizung, Batterie) ist ein vom Installateur
|
||||
gewähltes Etikett: Die Engine liest es nicht, um zu entscheiden.
|
||||
|
||||
Die App nutzt es, um die Bedienreihenfolge **nach Domänen** darzustellen: Man ordnet die
|
||||
Domänen untereinander, dann die Verbraucher innerhalb jeder Domäne. Bei der
|
||||
Inbetriebnahme schlägt sie vor: Elektrofahrzeug, Warmwasser, Klimatisierung, Heizung. Da
|
||||
alles auf der einen Liste beruht, müssen die Verbraucher einer Domäne nicht
|
||||
aufeinanderfolgen: Ein Zusatz-Warmwasserbereiter kann **ganz zuletzt** bedient werden,
|
||||
nach der Heizung, und eine Wallbox kann vor dem Warmwasser kommen, eine andere danach.
|
||||
|
||||
```mermaid
|
||||
flowchart LR
|
||||
subgraph AV["Vorgeschlagene Reihenfolge"]
|
||||
direction TB
|
||||
a1["1 · Wallbox Garage"] --> a2["2 · Wallbox Gäste"] --> a3["3 · Warmwasser Haupt"] --> a4["4 · Warmwasser Zusatz"] --> a5["5 · Wärmepumpe"]
|
||||
end
|
||||
subgraph AP["Nach der Einstellung"]
|
||||
direction TB
|
||||
b1["1 · Wallbox Garage"] --> b2["2 · Warmwasser Haupt"] --> b3["3 · Wallbox Gäste"] --> b4["4 · Wärmepumpe"] --> b5["5 · Warmwasser Zusatz"]
|
||||
end
|
||||
AV ==>|"nur Ränge ändern sich"| AP
|
||||
|
||||
classDef ev stroke:#3b82f6,stroke-width:3px
|
||||
classDef ecs stroke:#ef4444,stroke-width:3px
|
||||
classDef chauf stroke:#f59e0b,stroke-width:3px
|
||||
class a1,a2,b1,b3 ev
|
||||
class a3,a4,b2,b5 ecs
|
||||
class a5,b4 chauf
|
||||
```
|
||||
|
||||
Blauer Rand: Elektrofahrzeug · rot: Warmwasser · orange: Heizung.
|
||||
|
||||
!!! tip "Ränge bei der Inbetriebnahme festlegen"
|
||||
Eine erkannte Wallbox wird automatisch **ans Ende der Liste** gesetzt, unabhängig von
|
||||
ihrer Domäne. Zwei Verbraucher mit gleichem Rang werden über ihre Kennung getrennt –
|
||||
das hat niemand so gewählt. Legen Sie die Reihenfolge bei der Inbetriebnahme in der App
|
||||
fest.
|
||||
|
||||
### Die Grenzen jedes Verbrauchers
|
||||
|
||||
Jeder Verbraucher hat vom Installateur eingetragene Grenzen, die **jede** Entscheidung
|
||||
|
||||
@ -7,6 +7,48 @@ SG-Ready heat pump, relays. It is free software (GPL-3.0) and it is the one that
|
||||
in the **Community** edition. This page describes its logic for installers and
|
||||
integrators; the following pages detail each feature.
|
||||
|
||||
## Overview
|
||||
|
||||
```mermaid
|
||||
flowchart TB
|
||||
CPT["Grid meter<br/>current per phase, export, import"]
|
||||
BAT["Battery<br/>state of charge"]
|
||||
APP["App<br/>one-off requests"]
|
||||
CFG["Installer settings<br/>ranks, bounds, obligations"]
|
||||
|
||||
subgraph M["Energy engine, on the box"]
|
||||
PROT["Overload protection<br/>on every measurement, overrides"]
|
||||
subgraph C["Allocation cycle, every minute"]
|
||||
C1["1. Measurement and draw margin"] --> C2["2. Charging deadlines"]
|
||||
C2 --> C3["3. Battery reserve"]
|
||||
C3 --> C4["4. Eco pass<br/>one-off requests, obligations"]
|
||||
C4 --> C5["5. Comfort pass<br/>surplus in cascade, by rank"]
|
||||
C5 --> C6["6. One command per load"]
|
||||
end
|
||||
AD["Adapters<br/>bounds and locks of each load"]
|
||||
end
|
||||
|
||||
OPT["Optimizer, optional<br/>proposes the allocation"]
|
||||
|
||||
VE["EV chargers"]
|
||||
ECS["Water heaters<br/>relay or adjustable"]
|
||||
PAC["SG-Ready heat pump"]
|
||||
REL["Relays"]
|
||||
|
||||
CPT --> PROT
|
||||
CPT --> C1
|
||||
BAT --> C3
|
||||
APP --> C4
|
||||
CFG --> C
|
||||
OPT -. "plan" .-> C6
|
||||
C6 --> AD
|
||||
PROT --> AD
|
||||
AD --> VE & ECS & PAC & REL
|
||||
```
|
||||
|
||||
Overload protection and the adapters always stay with the engine: an
|
||||
[optimizer](../optimiseur/index.md), if connected, only proposes the allocation.
|
||||
|
||||
## Two loops, two priorities
|
||||
|
||||
The engine keeps safety apart from allocation. They are two separate loops, running at
|
||||
@ -65,6 +107,47 @@ On every cycle, the engine applies the same steps, in the same order.
|
||||
6. **One command per load.** The guaranteed need and the surplus share of the same load
|
||||
are merged: each load receives a single setpoint, with its reason.
|
||||
|
||||
### Ranks and domains
|
||||
|
||||
The engine knows **only one list**: each load has a rank, across all categories, and the
|
||||
cascade follows that rank. A load's **domain** (electric vehicle, domestic hot water, air
|
||||
conditioning, heating, battery) is a label chosen by the installer: the engine does not
|
||||
read it to decide.
|
||||
|
||||
The app uses it to present the service order **by domain**: you set the order of the
|
||||
domains, then the order of the loads within each domain. At commissioning it proposes:
|
||||
electric vehicle, domestic hot water, air conditioning, heating. Since everything rests on
|
||||
the single list, nothing forces the loads of a domain to follow each other: a backup water
|
||||
heater can be served **last of all**, after the heating, and one charger can come before
|
||||
the water heater while another comes after.
|
||||
|
||||
```mermaid
|
||||
flowchart LR
|
||||
subgraph AV["Proposed order"]
|
||||
direction TB
|
||||
a1["1 · EV garage"] --> a2["2 · EV visitor"] --> a3["3 · Main water heater"] --> a4["4 · Backup water heater"] --> a5["5 · Heat pump"]
|
||||
end
|
||||
subgraph AP["After adjustment"]
|
||||
direction TB
|
||||
b1["1 · EV garage"] --> b2["2 · Main water heater"] --> b3["3 · EV visitor"] --> b4["4 · Heat pump"] --> b5["5 · Backup water heater"]
|
||||
end
|
||||
AV ==>|"only ranks change"| AP
|
||||
|
||||
classDef ev stroke:#3b82f6,stroke-width:3px
|
||||
classDef ecs stroke:#ef4444,stroke-width:3px
|
||||
classDef chauf stroke:#f59e0b,stroke-width:3px
|
||||
class a1,a2,b1,b3 ev
|
||||
class a3,a4,b2,b5 ecs
|
||||
class a5,b4 chauf
|
||||
```
|
||||
|
||||
Blue border: electric vehicle · red: domestic hot water · orange: heating.
|
||||
|
||||
!!! tip "Set the ranks at commissioning"
|
||||
A detected charger is added automatically **at the end of the list**, whatever its
|
||||
domain. Two loads with the same rank are separated by their identifier, which nobody
|
||||
chose. Set the order in the app at commissioning.
|
||||
|
||||
### The bounds of each load
|
||||
|
||||
Each load carries bounds entered by the installer, which **every** decision respects,
|
||||
|
||||
@ -7,6 +7,48 @@ pompe à chaleur SG-Ready, relais. Il est libre (GPL-3.0) et c'est lui qui déci
|
||||
version **Community**. Cette page décrit sa logique pour l'installateur et l'intégrateur ;
|
||||
les pages suivantes détaillent chaque fonction.
|
||||
|
||||
## Vue d'ensemble
|
||||
|
||||
```mermaid
|
||||
flowchart TB
|
||||
CPT["Compteur de tête<br/>courant par phase, injection, soutirage"]
|
||||
BAT["Batterie<br/>état de charge"]
|
||||
APP["Application<br/>demandes ponctuelles"]
|
||||
CFG["Réglages de l'installateur<br/>rangs, bornes, obligations"]
|
||||
|
||||
subgraph M["Moteur d'énergie, sur la box"]
|
||||
PROT["Protection contre la surcharge<br/>à chaque mesure, prioritaire"]
|
||||
subgraph C["Cycle de répartition, chaque minute"]
|
||||
C1["1. Mesure et marge de soutirage"] --> C2["2. Recharges à échéance"]
|
||||
C2 --> C3["3. Réserve batterie"]
|
||||
C3 --> C4["4. Passe éco<br/>demandes ponctuelles, obligations"]
|
||||
C4 --> C5["5. Passe confort<br/>surplus en cascade, par rang"]
|
||||
C5 --> C6["6. Une commande par charge"]
|
||||
end
|
||||
AD["Adaptateurs<br/>bornes et verrous de chaque charge"]
|
||||
end
|
||||
|
||||
OPT["Optimiseur, en option<br/>propose la répartition"]
|
||||
|
||||
VE["Bornes de recharge"]
|
||||
ECS["Chauffe-eau<br/>à relais ou modulable"]
|
||||
PAC["Pompe à chaleur SG-Ready"]
|
||||
REL["Relais"]
|
||||
|
||||
CPT --> PROT
|
||||
CPT --> C1
|
||||
BAT --> C3
|
||||
APP --> C4
|
||||
CFG --> C
|
||||
OPT -. "plan" .-> C6
|
||||
C6 --> AD
|
||||
PROT --> AD
|
||||
AD --> VE & ECS & PAC & REL
|
||||
```
|
||||
|
||||
La protection contre la surcharge et les adaptateurs restent au moteur dans tous les cas :
|
||||
un [optimiseur](../optimiseur/index.md), s'il est branché, ne propose que la répartition.
|
||||
|
||||
## Deux boucles, deux priorités
|
||||
|
||||
Le moteur sépare la sécurité de la répartition. Ce sont deux boucles distinctes, qui ne
|
||||
@ -67,6 +109,47 @@ active. La répartition reprend au cycle qui suit le retour du compteur.
|
||||
6. **Une seule commande par charge.** Le besoin garanti et la part de surplus d'une même
|
||||
charge sont fusionnés : chaque charge reçoit une seule consigne, avec son motif.
|
||||
|
||||
### Les rangs et les domaines
|
||||
|
||||
Le moteur ne connaît **qu'une seule liste** : chaque charge a un rang, toutes catégories
|
||||
confondues, et la cascade suit ce rang. Le **domaine** d'une charge (véhicule électrique,
|
||||
eau chaude sanitaire, climatisation, chauffage, batterie) est une étiquette choisie par
|
||||
l'installateur : le moteur ne la lit pas pour décider.
|
||||
|
||||
L'application s'en sert pour présenter l'ordre de service **par domaines** : on règle
|
||||
l'ordre des domaines entre eux, puis l'ordre des charges dans chaque domaine. À la mise en
|
||||
service, elle propose : véhicule électrique, eau chaude sanitaire, climatisation,
|
||||
chauffage. Comme tout repose sur la liste unique, rien n'oblige les charges d'un domaine à
|
||||
se suivre : un chauffe-eau d'appoint peut être servi **en tout dernier**, après le
|
||||
chauffage, et une borne peut passer avant le chauffe-eau tandis qu'une autre passe après.
|
||||
|
||||
```mermaid
|
||||
flowchart LR
|
||||
subgraph AV["Ordre proposé"]
|
||||
direction TB
|
||||
a1["1 · VE garage"] --> a2["2 · VE visiteur"] --> a3["3 · Chauffe-eau principal"] --> a4["4 · Chauffe-eau d'appoint"] --> a5["5 · PAC"]
|
||||
end
|
||||
subgraph AP["Après réglage"]
|
||||
direction TB
|
||||
b1["1 · VE garage"] --> b2["2 · Chauffe-eau principal"] --> b3["3 · VE visiteur"] --> b4["4 · PAC"] --> b5["5 · Chauffe-eau d'appoint"]
|
||||
end
|
||||
AV ==>|"on ne change que des rangs"| AP
|
||||
|
||||
classDef ev stroke:#3b82f6,stroke-width:3px
|
||||
classDef ecs stroke:#ef4444,stroke-width:3px
|
||||
classDef chauf stroke:#f59e0b,stroke-width:3px
|
||||
class a1,a2,b1,b3 ev
|
||||
class a3,a4,b2,b5 ecs
|
||||
class a5,b4 chauf
|
||||
```
|
||||
|
||||
Bordure bleue : véhicule électrique · rouge : eau chaude sanitaire · orange : chauffage.
|
||||
|
||||
!!! tip "Poser les rangs à la mise en service"
|
||||
Une borne détectée est ajoutée d'office **en fin de liste**, quel que soit son domaine.
|
||||
Deux charges au même rang sont départagées par leur identifiant, ce qui n'est le choix
|
||||
de personne. Réglez l'ordre dans l'application à la mise en service.
|
||||
|
||||
### Les bornes de chaque charge
|
||||
|
||||
Chaque charge porte des bornes saisies par l'installateur, que **toute** décision
|
||||
|
||||
@ -50,7 +50,12 @@ markdown_extensions:
|
||||
permalink: true
|
||||
- pymdownx.highlight:
|
||||
anchor_linenums: true
|
||||
- pymdownx.superfences
|
||||
- pymdownx.superfences:
|
||||
# Schémas Mermaid (page « Comment le moteur décide ») : Material les dessine côté navigateur.
|
||||
custom_fences:
|
||||
- name: mermaid
|
||||
class: mermaid
|
||||
format: !!python/name:pymdownx.superfences.fence_code_format
|
||||
- pymdownx.details
|
||||
- pymdownx.inlinehilite
|
||||
- pymdownx.tabbed:
|
||||
|
||||
Loading…