824 lines
30 KiB
JSON
824 lines
30 KiB
JSON
{
|
|
"group": {
|
|
"desc": "DER AC controls model.",
|
|
"groups": [
|
|
{
|
|
"comments": [
|
|
"Power Factor Settings"
|
|
],
|
|
"desc": "Power factor setpoint when injecting active power.",
|
|
"label": "Power Factor (W Inj) ",
|
|
"name": "PFWInj",
|
|
"points": [
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor setpoint when injecting active power.",
|
|
"label": "Power Factor (W Inj) ",
|
|
"name": "PF",
|
|
"sf": "PF_SF",
|
|
"size": 1,
|
|
"type": "uint16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor excitation setpoint when injecting active power.",
|
|
"label": "Power Factor Excitation (W Inj)",
|
|
"name": "Ext",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Power factor over-excited excitation.",
|
|
"label": "Over-Excited",
|
|
"name": "OVER_EXCITED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Power factor under-excited excitation.",
|
|
"label": "Under-Excited",
|
|
"name": "UNDER_EXCITED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
}
|
|
],
|
|
"type": "sync"
|
|
},
|
|
{
|
|
"desc": "Reversion power factor setpoint when injecting active power.",
|
|
"label": "Reversion Power Factor (W Inj) ",
|
|
"name": "PFWInjRvrt",
|
|
"points": [
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion power factor setpoint when injecting active power.",
|
|
"label": "Reversion Power Factor (W Inj) ",
|
|
"name": "PF",
|
|
"sf": "PF_SF",
|
|
"size": 1,
|
|
"type": "uint16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion power factor excitation setpoint when injecting active power.",
|
|
"label": "Reversion PF Excitation (W Inj)",
|
|
"name": "Ext",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Power factor over-excited excitation.",
|
|
"label": "Over-Excited",
|
|
"name": "OVER_EXCITED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Power factor under-excited excitation.",
|
|
"label": "Under-Excited",
|
|
"name": "UNDER_EXCITED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
}
|
|
],
|
|
"type": "sync"
|
|
},
|
|
{
|
|
"desc": "Power factor setpoint when absorbing active power.",
|
|
"label": "Power Factor (W Abs) ",
|
|
"name": "PFWAbs",
|
|
"points": [
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor setpoint when absorbing active power.",
|
|
"label": "Power Factor (W Abs) ",
|
|
"name": "PF",
|
|
"sf": "PF_SF",
|
|
"size": 1,
|
|
"type": "uint16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor excitation setpoint when absorbing active power.",
|
|
"label": "Power Factor Excitation (W Abs)",
|
|
"name": "Ext",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Power factor over-excited excitation.",
|
|
"label": "Over-Excited",
|
|
"name": "OVER_EXCITED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Power factor under-excited excitation.",
|
|
"label": "Under-Excited",
|
|
"name": "UNDER_EXCITED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
}
|
|
],
|
|
"type": "sync"
|
|
},
|
|
{
|
|
"desc": "Reversion power factor setpoint when absorbing active power.",
|
|
"label": "Reversion Power Factor (W Abs) ",
|
|
"name": "PFWAbsRvrt",
|
|
"points": [
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion power factor setpoint when absorbing active power.",
|
|
"label": "Reversion Power Factor (W Abs) ",
|
|
"name": "PF",
|
|
"sf": "PF_SF",
|
|
"size": 1,
|
|
"type": "uint16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion power factor excitation setpoint when absorbing active power.",
|
|
"label": "Reversion PF Excitation (W Abs)",
|
|
"name": "Ext",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Power factor over-excited excitation.",
|
|
"label": "Over-Excited",
|
|
"name": "OVER_EXCITED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Power factor under-excited excitation.",
|
|
"label": "Under-Excited",
|
|
"name": "UNDER_EXCITED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
}
|
|
],
|
|
"type": "sync"
|
|
}
|
|
],
|
|
"label": "DER AC Controls",
|
|
"name": "DERCtlAC",
|
|
"points": [
|
|
{
|
|
"desc": "DER AC controls model ID.",
|
|
"label": "Model ID",
|
|
"mandatory": "M",
|
|
"name": "ID",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "uint16",
|
|
"value": 704
|
|
},
|
|
{
|
|
"desc": "DER AC controls model length.",
|
|
"label": "Model Length",
|
|
"mandatory": "M",
|
|
"name": "L",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "uint16",
|
|
"value": 65
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"comments": [
|
|
"Set Power Factor (when injecting active power)"
|
|
],
|
|
"desc": "Power factor enable when injecting active power.",
|
|
"label": "Power Factor Enable (W Inj) Enable",
|
|
"name": "PFWInjEna",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor reversion timer when injecting active power enable.",
|
|
"label": "Power Factor Reversion Enable (W Inj)",
|
|
"name": "PFWInjEnaRvrt",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor reversion timer when injecting active power.",
|
|
"label": "PF Reversion Time (W Inj)",
|
|
"name": "PFWInjRvrtTms",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"desc": "Power factor reversion time remaining when injecting active power.",
|
|
"label": "PF Reversion Time Rem (W Inj)",
|
|
"name": "PFWInjRvrtRem",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"comments": [
|
|
"Set Power Factor (when absorbing active power)"
|
|
],
|
|
"desc": "Power factor enable when absorbing active power.",
|
|
"label": "Power Factor Enable (W Abs) Enable",
|
|
"name": "PFWAbsEna",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor reversion timer when absorbing active power enable.",
|
|
"label": "Power Factor Reversion Enable (W Abs)",
|
|
"name": "PFWAbsEnaRvrt",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Power factor reversion timer when absorbing active power.",
|
|
"label": "PF Reversion Time (W Abs)",
|
|
"name": "PFWAbsRvrtTms",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"desc": "Power factor reversion time remaining when absorbing active power.",
|
|
"label": "PF Reversion Time Rem (W Abs)",
|
|
"name": "PFWAbsRvrtRem",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"comments": [
|
|
"Limit Maximum Active Power Generation"
|
|
],
|
|
"desc": "Limit maximum active power percent enable.",
|
|
"label": "Limit Max Power Pct Enable",
|
|
"name": "WMaxLimPctEna",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Limit maximum active power percent value.",
|
|
"label": "Limit Max Power Pct Setpoint",
|
|
"name": "WMaxLimPct",
|
|
"sf": "WMaxLimPct_SF",
|
|
"size": 1,
|
|
"type": "uint16",
|
|
"units": "Pct"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion limit maximum active power percent value.",
|
|
"label": "Reversion Limit Max Power Pct",
|
|
"name": "WMaxLimPctRvrt",
|
|
"sf": "WMaxLimPct_SF",
|
|
"size": 1,
|
|
"type": "uint16",
|
|
"units": "Pct"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion limit maximum active power percent value enable.",
|
|
"label": "Reversion Limit Max Power Pct Enable",
|
|
"name": "WMaxLimPctEnaRvrt",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Limit maximum active power percent reversion time.",
|
|
"label": "Limit Max Power Pct Reversion Time",
|
|
"name": "WMaxLimPctRvrtTms",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"desc": "Limit maximum active power percent reversion time remaining.",
|
|
"label": "Limit Max Power Pct Rev Time Rem",
|
|
"name": "WMaxLimPctRvrtRem",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"comments": [
|
|
"Set Active Power Level (may be negative for charging)"
|
|
],
|
|
"desc": "Set active power enable.",
|
|
"label": "Set Active Power Enable",
|
|
"name": "WSetEna",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Set active power mode.",
|
|
"label": "Set Active Power Mode",
|
|
"name": "WSetMod",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Active power setting is percentage of maximum active power.",
|
|
"label": "Active Power As Max Percent",
|
|
"name": "W_MAX_PCT",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Active power setting is in watts.",
|
|
"label": "Active Power As Watts",
|
|
"name": "WATTS",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Active power setting value in watts.",
|
|
"label": "Active Power Setpoint (W)",
|
|
"name": "WSet",
|
|
"sf": "WSet_SF",
|
|
"size": 2,
|
|
"type": "int32",
|
|
"units": "W"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion active power setting value in watts.",
|
|
"label": "Reversion Active Power (W)",
|
|
"name": "WSetRvrt",
|
|
"sf": "WSet_SF",
|
|
"size": 2,
|
|
"type": "int32",
|
|
"units": "W"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Active power setting value as percent.",
|
|
"label": "Active Power Setpoint (Pct)",
|
|
"name": "WSetPct",
|
|
"sf": "WSetPct_SF",
|
|
"size": 1,
|
|
"type": "int16",
|
|
"units": "Pct"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion active power setting value as percent.",
|
|
"label": "Reversion Active Power (Pct)",
|
|
"name": "WSetPctRvrt",
|
|
"sf": "WSetPct_SF",
|
|
"size": 1,
|
|
"type": "int16",
|
|
"units": "Pct"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion active power function enable.",
|
|
"label": "Reversion Active Power Enable",
|
|
"name": "WSetEnaRvrt",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Set active power reversion time.",
|
|
"label": "Active Power Reversion Time",
|
|
"name": "WSetRvrtTms",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"desc": "Set active power reversion time remaining.",
|
|
"label": "Active Power Rev Time Rem",
|
|
"name": "WSetRvrtRem",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"comments": [
|
|
"Set Reacitve Power Level"
|
|
],
|
|
"desc": "Set reactive power enable.",
|
|
"label": "Set Reactive Power Enable",
|
|
"name": "VarSetEna",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Set reactive power mode.",
|
|
"label": "Set Reactive Power Mode",
|
|
"name": "VarSetMod",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Reactive power setting is percent of maximum active power.",
|
|
"label": "Reactive Power As Watt Max Pct",
|
|
"name": "W_MAX_PCT",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Reactive power setting is percent of maximum reactive power.",
|
|
"label": "Reactive Power As Var Max Pct",
|
|
"name": "VAR_MAX_PCT",
|
|
"value": 1
|
|
},
|
|
{
|
|
"desc": "Reactive power setting is percent of available reactive power.",
|
|
"label": "Reactive Power As Var Avail Pct",
|
|
"name": "VAR_AVAIL_PCT",
|
|
"value": 2
|
|
},
|
|
{
|
|
"desc": "Reactive power is in vars.",
|
|
"label": "Reactive Power As Vars",
|
|
"name": "VARS",
|
|
"value": 3
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reactive power priority.",
|
|
"label": "Reactive Power Priority",
|
|
"name": "VarSetPri",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Active power priority.",
|
|
"label": "Active Power Priority",
|
|
"name": "ACTIVE",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Reactive power priority.",
|
|
"label": "Reactive Power Priority",
|
|
"name": "REACTIVE",
|
|
"value": 1
|
|
},
|
|
{
|
|
"desc": "IEEE 1547-2018 power priority mode.",
|
|
"label": "IEEE 1547 Power Priority",
|
|
"name": "IEEE_1547",
|
|
"value": 2
|
|
},
|
|
{
|
|
"desc": "Track PF setting derived from current active and reactive power settings.",
|
|
"label": "PF Power Priority",
|
|
"name": "PF",
|
|
"value": 3
|
|
},
|
|
{
|
|
"desc": "Power priority is vendor specific mode.",
|
|
"label": "Vendor Power Priority",
|
|
"name": "VENDOR",
|
|
"value": 4
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reactive power setting value in vars.",
|
|
"label": "Reactive Power Setpoint (Vars)",
|
|
"name": "VarSet",
|
|
"sf": "VarSet_SF",
|
|
"size": 2,
|
|
"type": "int32",
|
|
"units": "Var"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion reactive power setting value in vars.",
|
|
"label": "Reversion Reactive Power (Vars)",
|
|
"name": "VarSetRvrt",
|
|
"sf": "VarSet_SF",
|
|
"size": 2,
|
|
"type": "int32",
|
|
"units": "Var"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reactive power setting value as percent.",
|
|
"label": "Reactive Power Setpoint (Pct)",
|
|
"name": "VarSetPct",
|
|
"sf": "VarSetPct_SF",
|
|
"size": 1,
|
|
"type": "int16",
|
|
"units": "Pct"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion reactive power setting value as percent.",
|
|
"label": "Reversion Reactive Power (Pct)",
|
|
"name": "VarSetPctRvrt",
|
|
"sf": "VarSetPct_SF",
|
|
"size": 1,
|
|
"type": "int16",
|
|
"units": "Pct"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Reversion reactive power function enable.",
|
|
"label": "Reversion Reactive Power Enable",
|
|
"name": "VarSetEnaRvrt",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Function is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Function is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Set reactive power reversion time.",
|
|
"label": "Reactive Power Reversion Time",
|
|
"name": "VarSetRvrtTms",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"desc": "Set reactive power reversion time remaining.",
|
|
"label": "Reactive Power Rev Time Rem",
|
|
"name": "VarSetRvrtRem",
|
|
"size": 2,
|
|
"type": "uint32",
|
|
"units": "Secs"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"comments": [
|
|
"Ramp Rate"
|
|
],
|
|
"desc": "Ramp rate for increases in active power during normal generation.",
|
|
"label": "Normal Ramp Rate",
|
|
"name": "WRmp",
|
|
"size": 1,
|
|
"type": "uint16",
|
|
"units": "%Max/Sec"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Ramp rate reference unit for increases in active power or current during normal generation.",
|
|
"label": "Normal Ramp Rate Reference",
|
|
"name": "WRmpRef",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Ramp based on percent of max current per second.",
|
|
"label": "Max Current Ramp",
|
|
"name": "A_MAX",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Ramp based on percent of max active power per second.",
|
|
"label": "Max Active Power Ramp",
|
|
"name": "W_MAX",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Ramp rate based on max reactive power per second.",
|
|
"label": "Reactive Power Ramp Rate",
|
|
"name": "VarRmp",
|
|
"size": 1,
|
|
"type": "uint16",
|
|
"units": "%Max/Sec"
|
|
},
|
|
{
|
|
"access": "RW",
|
|
"desc": "Anti-islanding enable.",
|
|
"label": "Anti-Islanding Enable",
|
|
"name": "AntiIslEna",
|
|
"size": 1,
|
|
"symbols": [
|
|
{
|
|
"desc": "Anti-islanding is disabled.",
|
|
"label": "Disabled",
|
|
"name": "DISABLED",
|
|
"value": 0
|
|
},
|
|
{
|
|
"desc": "Anti-islanding is enabled.",
|
|
"label": "Enabled",
|
|
"name": "ENABLED",
|
|
"value": 1
|
|
}
|
|
],
|
|
"type": "enum16"
|
|
},
|
|
{
|
|
"comments": [
|
|
"Scale Factors"
|
|
],
|
|
"desc": "Power factor scale factor.",
|
|
"label": "Power Factor Scale Factor",
|
|
"name": "PF_SF",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "sunssf"
|
|
},
|
|
{
|
|
"desc": "Limit maximum power scale factor.",
|
|
"label": "Limit Max Power Scale Factor",
|
|
"name": "WMaxLimPct_SF",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "sunssf"
|
|
},
|
|
{
|
|
"desc": "Active power scale factor.",
|
|
"label": "Active Power Scale Factor",
|
|
"name": "WSet_SF",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "sunssf"
|
|
},
|
|
{
|
|
"desc": "Active power pct scale factor.",
|
|
"label": "Active Power Pct Scale Factor",
|
|
"name": "WSetPct_SF",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "sunssf"
|
|
},
|
|
{
|
|
"desc": "Reactive power scale factor.",
|
|
"label": "Reactive Power Scale Factor",
|
|
"name": "VarSet_SF",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "sunssf"
|
|
},
|
|
{
|
|
"desc": "Reactive power pct scale factor.",
|
|
"label": "Reactive Power Pct Scale Factor",
|
|
"name": "VarSetPct_SF",
|
|
"size": 1,
|
|
"static": "S",
|
|
"type": "sunssf"
|
|
}
|
|
],
|
|
"type": "group"
|
|
},
|
|
"id": 704
|
|
} |