"group": {
"desc": "Inverter Controls Extended Measurements and Status ",
"label": "Measurements_Status",
"name": "status",
"points": [
{
"desc": "Model identifier",
"label": "Model ID",
"mandatory": "M",
"name": "ID",
"size": 1,
"static": "S",
"type": "uint16",
"value": 122
},
{
"desc": "Model length",
"label": "Model Length",
"mandatory": "M",
"name": "L",
"size": 1,
"static": "S",
"type": "uint16"
},
{
"desc": "PV inverter present/available status. Enumerated value.",
"label": "PVConn",
"mandatory": "M",
"name": "PVConn",
"size": 1,
"symbols": [
{
"name": "CONNECTED",
"value": 0
},
{
"name": "AVAILABLE",
"value": 1
},
{
"name": "OPERATING",
"value": 2
},
{
"name": "TEST",
"value": 3
}
],
"type": "bitfield16"
},
{
"desc": "Storage inverter present/available status. Enumerated value.",
"label": "StorConn",
"mandatory": "M",
"name": "StorConn",
"size": 1,
"symbols": [
{
"name": "CONNECTED",
"value": 0
},
{
"name": "AVAILABLE",
"value": 1
},
{
"name": "OPERATING",
"value": 2
},
{
"name": "TEST",
"value": 3
}
],
"type": "bitfield16"
},
{
"desc": "ECP connection status: disconnected=0 connected=1.",
"label": "ECPConn",
"mandatory": "M",
"name": "ECPConn",
"size": 1,
"symbols": [
{
"name": "CONNECTED",
"value": 0
}
],
"type": "bitfield16"
},
{
"desc": "AC lifetime active (real) energy output.",
"label": "ActWh",
"name": "ActWh",
"size": 4,
"type": "acc64",
"units": "Wh"
},
{
"desc": "AC lifetime apparent energy output.",
"label": "ActVAh",
"name": "ActVAh",
"size": 4,
"type": "acc64",
"units": "VAh"
},
{
"desc": "AC lifetime reactive energy output in quadrant 1.",
"label": "ActVArhQ1",
"name": "ActVArhQ1",
"size": 4,
"type": "acc64",
"units": "varh"
},
{
"desc": "AC lifetime reactive energy output in quadrant 2.",
"label": "ActVArhQ2",
"name": "ActVArhQ2",
"size": 4,
"type": "acc64",
"units": "varh"
},
{
"desc": "AC lifetime negative energy output in quadrant 3.",
"label": "ActVArhQ3",
"name": "ActVArhQ3",
"size": 4,
"type": "acc64",
"units": "varh"
},
{
"desc": "AC lifetime reactive energy output in quadrant 4.",
"label": "ActVArhQ4",
"name": "ActVArhQ4",
"size": 4,
"type": "acc64",
"units": "varh"
},
{
"desc": "Amount of VARs available without impacting watts output.",
"label": "VArAval",
"name": "VArAval",
"sf": "VArAval_SF",
"size": 1,
"type": "int16",
"units": "var"
},
{
"desc": "Scale factor for available VARs.",
"label": "VArAval_SF",
"name": "VArAval_SF",
"size": 1,
"type": "sunssf"
},
{
"desc": "Amount of Watts available.",
"label": "WAval",
"name": "WAval",
"sf": "WAval_SF",
"size": 1,
"type": "uint16",
"units": "var"
},
{
"desc": "Scale factor for available Watts.",
"label": "WAval_SF",
"name": "WAval_SF",
"size": 1,
"type": "sunssf"
},
{
"desc": "Bit Mask indicating setpoint limit(s) reached.",
"label": "StSetLimMsk",
"name": "StSetLimMsk",
"size": 2,
"symbols": [
{
"name": "WMax",
"value": 0
},
{
"name": "VAMax",
"value": 1
},
{
"name": "VArAval",
"value": 2
},
{
"name": "VArMaxQ1",
"value": 3
},
{
"name": "VArMaxQ2",
"value": 4
},
{
"name": "VArMaxQ3",
"value": 5
},
{
"name": "VArMaxQ4",
"value": 6
},
{
"name": "PFMinQ1",
"value": 7
},
{
"name": "PFMinQ2",
"value": 8
},
{
"name": "PFMinQ3",
"value": 9
},
{
"name": "PFMinQ4",
"value": 10
}
],
"type": "bitfield32"
},
{
"desc": "Bit Mask indicating which inverter controls are currently active.",
"label": "StActCtl",
"name": "StActCtl",
"size": 2,
"symbols": [
{
"name": "FixedW",
"value": 0
},
{
"name": "FixedVAR",
"value": 1
},
{
"name": "FixedPF",
"value": 2
},
{
"name": "Volt-VAr",
"value": 3
},
{
"name": "Freq-Watt-Param",
"value": 4
},
{
"name": "Freq-Watt-Curve",
"value": 5
},
{
"name": "Dyn-Reactive-Current",
"value": 6
},
{
"name": "LVRT",
"value": 7
},
{
"name": "HVRT",
"value": 8
},
{
"name": "Watt-PF",
"value": 9
},
{
"name": "Volt-Watt",
"value": 10
},
{
"name": "Scheduled",
"value": 12
},
{
"name": "LFRT",
"value": 13
},
{
"name": "HFRT",
"value": 14
}
],
"type": "bitfield32"
},
{
"desc": "Source of time synchronization.",
"label": "TmSrc",
"name": "TmSrc",
"size": 4,
"type": "string"
},
{
"desc": "Seconds since 01-01-2000 00:00 UTC",
"label": "Tms",
"name": "Tms",
"size": 2,
"type": "uint32",
"units": "Secs"
},
{
"desc": "Bit Mask indicating active ride-through status.",
"label": "RtSt",
"name": "RtSt",
"size": 1,
"symbols": [
{
"name": "LVRT_ACTIVE",
"value": 0
},
{
"name": "HVRT_ACTIVE",
"value": 1
},
{
"name": "LFRT_ACTIVE",
"value": 2
},
{
"name": "HFRT_ACTIVE",
"value": 3
}
],
"type": "bitfield16"
},
{
"desc": "Isolation resistance.",
"label": "Ris",
"name": "Ris",
"sf": "Ris_SF",
"size": 1,
"type": "uint16",
"units": "ohms"
},
{
"desc": "Scale factor for isolation resistance.",
"label": "Ris_SF",
"name": "Ris_SF",
"size": 1,
"type": "sunssf"
}
],
"type": "group"
},
"id": 122
}