# Compteur ABB B2x
TESTING ETM CONSUMER
Le compteur d'énergie ABB B2x communique en **Modbus RTU** sur le bus RS485 du
hub. Mesure triphasée (tensions, courants et puissances par phase).
## 1. Matériel requis
- Compteur ABB B2x
- Adaptateur USB↔RS485 côté hub
- Câble bus 2 fils (A/B) + masse
## 2. Raccordement RS485
A↔A, B↔B, masse commune, terminaison **120 Ω** en bout de bus.
## 3. Adressage Modbus
Adresse esclave unique sur le bus (`1`–`254`, défaut `1`).
## 4. Ajout dans PowerSync
Ajout par **découverte automatique** ou **manuel** (saisie de l'adresse esclave).
Voir [Ajouter un appareil](../../installation/application.md).
---
## Référence
**Manufacturer:** ABB
**Plugin:** `AbbB2x`
#### Supported models
| Model | Role | Transport | Pairing | Quantities |
| --- | --- | --- | --- | --- |
| **ABB B2x energy meter** | Energy meter | Modbus RTU | Auto-discovery / Manual | 14 |
#### Per-model detail
??? abstract "ABB B2x energy meter — `abbB2x`"
_Discovery parameters:_
| Key | Label | Type | Range | Default |
| --- | --- | --- | --- | --- |
| `slaveAddress` | Modbus slave address | uint | 1–254 | `1` |
_Settings:_
| Key | Label | Type | Range | Default | Read-only |
| --- | --- | --- | --- | --- | --- |
| `slaveAddress` | Modbus slave address | uint | 1–254 | `1` | yes |
| `modbusMasterUuid` | Modbus RTU master | QString | — | — | yes |
_Measured quantities:_
| Key | Quantity | Type | Unit |
| --- | --- | --- | --- |
| `connected` | Connected | bool | — |
| `currentPower` | Current power | double | Watt |
| `totalEnergyConsumed` | Total energy consumed | double | KiloWattHour |
| `totalEnergyProduced` | Total energy produced | double | KiloWattHour |
| `frequency` | Frequency | double | Hertz |
| `voltagePhaseA` | Voltage phase A | double | Volt |
| `voltagePhaseB` | Voltage phase B | double | Volt |
| `voltagePhaseC` | Voltage phase C | double | Volt |
| `currentPhaseA` | Current phase A | double | Ampere |
| `currentPhaseB` | Current phase B | double | Ampere |
| `currentPhaseC` | Current phase C | double | Ampere |
| `currentPowerPhaseA` | Current power phase A | double | Watt |
| `currentPowerPhaseB` | Current power phase B | double | Watt |
| `currentPowerPhaseC` | Current power phase C | double | Watt |