AC-7 asks for the meterSlaveId parameter to be advanced. That property
does not exist on nymea 1.15.2 param types: the metadata verifier
rejects unknown fields, so adding it makes the whole plugin fail to
load rather than merely hiding a parameter.
Measured by loading the plugin JSON, with and without the flag, into a
PluginMetadata linked against the installed libnymea, rather than read
from an upstream tree that may differ from the package.
Also records the three other divergences the multi unit ID work runs
into, two of which predate it.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
setupThing() only knew about sunspecConnection and solarEdgeConnection, so a
froniusConnection thing fell into the final Q_ASSERT_X. In a release build the
assert is compiled out, setupThing() returns without calling info->finish(),
and the pairing hangs until the setup times out - with no message at all. In a
debug build nymead dies on the assert instead.
Take the same branch as the two vendors that already work: createConnection()
already reads the slave ID and picks the byte order for froniusConnection, so
no new logic is needed.
postSetupThing() and thingRemoved() are unchanged on purpose. The former only
special cases solarEdgeConnection, for the battery search a Fronius must not
run, and registers the refresh timer for every thing. The latter is keyed on
m_sunSpecConnections, which createConnection() now populates for Fronius as
well.
Makes the four cases of tst_sunspecplugin pass.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
The existing suite only exercises free functions and the plugin JSON, so it
cannot see whether a thing class is dispatched at all. A thing class missing
from the dispatch in setupThing() falls into the final Q_ASSERT_X: in a debug
build the process dies, in a release build the assert is compiled out and
setupThing() returns without ever calling info->finish(), leaving the pairing
stuck with no message.
Split the tests into two suites. The logic one keeps its former scope and its
single dependency on libnymea-sunspec. The new one instantiates the plugin
behind the real ThingManager of libnymea-core and a faked HardwareManager, so
the dispatch of setupThing(), postSetupThing() and thingRemoved() is covered.
No network access takes place: the faked monitor is never reachable, so the
plugin never attempts a Modbus connection.
The four new cases fail: froniusConnection is not dispatched yet.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
Adds a fronius vendor and a froniusConnection thing class alongside the
generic sunspec and solarEdge ones, following the SolarEdge mechanism but
none of its workarounds - no proprietary battery block and no PV
production computed by difference, since the GEN24 exposes model 160.
FroniusRules holds the vendor decisions as pure functions:
- discovery only keeps devices announcing Fronius as manufacturer;
- the byte order is the SunSpec default, not the forced big endian that
is specific to SolarEdge, and no endianness parameter is exposed;
- meterSlaveId defaults to 200, 0 meaning no meter on this connection;
- a hard 7 s floor on the poll interval. Polling faster can push the
inverter offline towards the vendor portal, and recovery needs an
AC+DC power cycle on site, so this is a guard in the code rather than
a configurable default;
- the registers the inverter accepts and then silently ignores are
refused before anything reaches the wire;
- the six HEMS battery modes map onto ChaGriSet, StorCtl_Mod, InWRte and
OutWRte, negative meaning charge;
- model 160 blocks are classified by IDStr, never by index: on a three
or four MPPT inverter the battery blocks are not in position 3 and 4.
Storages under a Fronius connection default revertTime to 300 s.
Setpoints now reread the scale factor before writing and read the written
registers back afterwards, reporting a mismatch through a new
controlHealthy state - the only defence against writes that are accepted
and then ignored without a Modbus exception.
Byte order and the revert timer semantics on model 124 are inferences, not
measurements; see specs/fronius-sunspec.md, H-2 and H-3.
setInOutWRteRvrtTms() existed but was never called. InOutWRte_RvrtTms is
the delay after which the inverter drops the setpoint and resumes its
native behaviour. Left at 0, a setpoint stays active indefinitely, HEMS
stopped, network lost or process crashed included - the battery stays
where the last command put it.
Add a per-thing revertTime parameter, 0..28800 s, defaulting to 0 so the
generic vendor keeps its current behaviour, and route every setpoint
through SunSpecStorageLogic::planSetpoint(). The plan orders the writes -
ChaGriSet, StorCtl_Mod, then the rates - and appends the revert timer
last, so the timer never starts counting against a setpoint that has not
been written yet.
Writes are issued sequentially rather than in parallel: the order is part
of the contract with the hardware.
onStorageBlockUpdated() fed chargingRate from wChaGra() and dischargingRate
from wDisChaGra(). Those are the gradients, in percent of WChaMax per
second, and read only on several inverters. The matching actions write
InWRte and OutWRte, in percent of WChaMax. The user wrote one quantity and
read back another.
Feed the two rate states from inWRte() and outWRte(), and keep the
gradients under names that cannot be mistaken for setpoints:
chargeGradient and dischargeGradient, read only.
enableDischarging was never reconciled either, while enableCharging was.
It stayed frozen on the last written value and drifted silently as soon as
the inverter changed StorCtl_Mod on its own. Reconcile both flags.
The mapping moves into SunSpecStorageLogic so it can be exercised on a
register dump without a running nymea.
chargingRate and dischargingRate map onto InWRte and OutWRte of model 124,
which are int16 setpoints ranging from -100.00 to +100.00 percent of
WChaMax. Declaring them as 0..100 makes a forced charge structurally
inexpressible: nymea rejects the negative action parameter before it ever
reaches the plugin.
Also fixes the default value, which was the boolean false on an int state.
One test per AC of specs/fronius-sunspec.md, named test_AC_<n>_<what>.
Definition criteria (value ranges, thing classes, defaults) are checked by
re-reading integrationpluginsunspec.json. Behaviour criteria run either on
a model 124 register dump fed to the real libnymea-sunspec model, or on the
pure logic units the plugin is about to grow.
All red at this point: sunspecstoragelogic and froniusrules do not exist
yet, so the suite does not compile. That is the expected starting state.
Vendor the sunspec plugin into this repo so the Fronius work and the
upstream storage fixes can live here. Sources only: build artefacts and
generated plugininfo headers are excluded.
libnymea-sunspec is deliberately NOT vendored - the plugin must stay
rebasable on upstream nymea, so it links against libnymea-sunspec-dev.
sunspec.pri resolves it via pkg-config, with a NYMEA_SUNSPEC_PATH
override for a local sysroot, mirroring modbus.pri.
See sunspec/VENDORED.md.