Patrick Schurig
abae49e058 sunspec: widen storage charge and discharge rate range
chargingRate and dischargingRate map onto InWRte and OutWRte of model 124,
which are int16 setpoints ranging from -100.00 to +100.00 percent of
WChaMax. Declaring them as 0..100 makes a forced charge structurally
inexpressible: nymea rejects the negative action parameter before it ever
reaches the plugin.

Also fixes the default value, which was the boolean false on an int state.
2026-07-31 10:20:05 +02:00
Patrick Schurig
bb842eea55 sunspec: vendor plugin sources from nymea-plugins-modbus 1.15.2
Vendor the sunspec plugin into this repo so the Fronius work and the
upstream storage fixes can live here. Sources only: build artefacts and
generated plugininfo headers are excluded.

libnymea-sunspec is deliberately NOT vendored - the plugin must stay
rebasable on upstream nymea, so it links against libnymea-sunspec-dev.
sunspec.pri resolves it via pkg-config, with a NYMEA_SUNSPEC_PATH
override for a local sysroot, mirroring modbus.pri.

See sunspec/VENDORED.md.